English Russian Spanish Portuguese French Arabic
HomeProductsHV and MV Switchgear

KYN 28A-12/24

Armored removable AC metal enclosed switchgear
Rated voltage: 12、24KV
Rated current: 630-3150A
Propose: Long-distance power transmission、 main distribution in substations、total incoming lines of large industrial parks
Temperature: -15°C~+40°C、Altitude<1000m
Standards: IEC 62271-200、IEC 62271-201
KYN 28A-12/24 - 华通大图
KYN 28A-12/24 - 华通大图
Application & Technical Parameters
Normal service conditions


1. Environmental conditions: -15℃~+40℃, and the average value measured within 24h shall not exceed 35℃;

2. The temperature conditions are as follows: the average value of daily relative humidity shall not exceed 95%; The average monthly relative humidity shall not exceed 90%; The average value of daily water vapor pressure shall not exceed 2.2kpa; The average monthly water vapor pressure shall not exceed 1.8kpa;

3. Mounting Height:≤1000m (Altitude)

4. The surrounding air is not obviously polluted by dust, smoke, corrosive or combustible gas, steam or salt mist;

5. Vibration or ground motion from the outside of switchgear and control equipment can be ignored;

6. The amplitude of electromagnetic interference induced in the secondary system shall not exceed 1.6kv .


Type meaning

KYN 28A-12KV

华通型号说明.png

KYN 28A-24KV

华通型号说明.png

Main technical parameters

KYN28A-12 

No.

Project

Unit

Parameters

1

Rated voltage

KV

3.6,7.2,12

2

Rated frequency

HZ

50

3

Rated current of circuit breaker

A

630,1250,1600,2000,2500,3150

4

Rated current of cabinet

A

630,1250,1600,2000,2500,3150

5

Rated short-time withstand current (4S)

KA

20,25,31.5,40

6

Rated peak withstand current (peak)

KA

50,63,80,100

7

Rated short-circuit breaking current

KA

20,25,31.5,40

8

Rated short-circuit making current (peak)

KA

50,63,80,100

9

Rated insulation level

1min power frequency withstand voltage

Between phases、Phase to ground

KV

24,32,42

Between fractures

KV

24,32,42

Lightning impulse withstand voltage

Between phases、Phase to ground

KV

40,60,75

Between fractures

KV

46,70,85

10

Degree of protection

 

The enclosure is IP4X, and the compartment is IP2X when the door of the circuit breaker room is opened

KYN28A-24

1.Technical parameter

No.

Project

Unit

Parameter

1

Rated Voltage

KV

24

2

Rated frequency  

HZ

50/60

3

Rated insulation level

Lightning impulse withstand voltage (peak)

KV

 

Phase to ground

60

 

Isolation fracture

79

1min power frequency withstand voltage (effective value)

   KV

125

145

Power frequency withstand voltage of auxiliary control circuit

V

2000

4

Rated current

A

630,1250,1600,2000,2500,3150

5

Rated short-circuit breaking curren

KA

20

31.5

6

Rated short-circuit making current (peak)

KA

50

80

7

Rated short-time withstand current (4S)

KA

20

31.5

8

Rated peak withstand current

KA

50

80

9

Rated voltage of auxiliary control circuit

A

DC/AC 110/220

10

Degree of protection

 

IP4X(Circuit breaker room door open or compartment:IP2X)

11

Overall dimension(W×D×H)

MM

800×1810×2380

1000×1810×2380

12

Weight

KG

840~1440

Note: the depth of overhead incoming and outgoing line cabinet is 2360mm


2、VS1-24 、VN2-24 Main technical parameters of vacuum circuit breaker

No.

Project

Unit

Parameter

1

Rated voltage

 

KV

24

2

Rated insulation level

1min power frequency withstand voltage (effective value)

60

 

Lightning impulse withstand voltage (peak)

125

3

Rated frequency  

HZ

50/60

4

Rated current

A

630,1250,1600,2000

630,1250,1600,2000,2500,3150

5

Rated short-circuit breaking current

 

KA

20

31.5

6

Rated short-circuit making current (peak)

50

80

7

Rated short-time withstand current(4s)

20

31.5

8

Rated peak withstand current

50

80

9

Rated breaking current of single capacitor bank

   
     A

630

10

Rated back-to-back capacitor bank breaking current

400

11

Rated short-circuit breaking current breaking times

 

Times

 50

12

Mechanical life

20000

13

Rated operating sequence

 

O-0.3S-CO-180S-CO


3、Technical parameters of spring operating mechanism

No.

Project

Unit

Parameter

1

Rated voltage

Closing trip coil

V

AC220,AC110,DC220,DC110

Opening trip coil

2

Rated current

Closing trip coil

A

AC220/DC220:1.1
AC1100/DC110:3.1

Opening trip coil

3

Energy storage motor power

W

100

4

Rated voltage of energy storage motor

S

AC220,AC110,DC220,DC110

5

Electric energy storage time

V

≤110

Structure and working principle

KYN28A-12


华通型号说明.png

Overall dimension(mm)

Height

 

2300

Width

Rated current below1250A

800

Rated current below1600A

1000

Depth

Cable incoming and outgoing

1500

Overhead incoming and outgoing

1660


Installation dimension(mm)

Cabinet width

Cabinet depth

L1

L2

L3

L4

800

1500 Cable

530

630

150

490

1660 Overhead

530

630

310

650

1000

1500 Cable

730

830

150

490

1660 Overhead

730

830

310

650


华通型号说明.png


KYN28A-24


华通图片.png

Main circuit scheme diagram

KYN28A-24  

Scheme No.

01

02

03

04

05

 

Primary circuit scheme

image.png 

 

 

image.png 

image.png 

image.png 

image.png 

Rated current

630~3150

Primary main electrical components

Vacuum circuit breaker VS1-24

1

1

1

1

1

Current transformerLZZB9-24

2

2

2

3

3

PT JDZ11-20/JDZX11-20

 

 

 

 

 

Fuse XRNP-24 0.5A

 

 

 

 

 

Grounding switch JN15-24

 

 

1

 

 

Lightning arrester HY5WZ-32/84

 

 

3

 

 

Purpose 

Power receiving and  feeding

Feeding

Feeding

Power receiving and  feeding

Feeding

Scheme No.

06

07

08

09

10

 

Primary circuit scheme

image.png 

image.png 

image.png 

image.png 

image.png 

Rated current

630~3150

Primary main electrical components

Vacuum circuit breaker VS1-24

1

1

1

1

1

Current transformerLZZB9-24

3

2

2

3

3

PT JDZ11-20/JDZX11-20

 

 

 

 

 

Fuse XRNP-24 0.5A

 

 

 

 

 

Grounding switch JN15-24

1

 

1

 

1

Lightning arrester HY5WZ-32/84

3

 

 

 

 

Purpose 

Feeding

Contact (right)

Contact (right)

Contact (left)

Contact (left)

Scheme No.

11

12

13

14

15

 

Primary circuit scheme

image.png 

image.png 

image.png 

image.png 

image.png 

Rated current

630~3150

Primary main electrical components

Vacuum circuit breaker VS1-24

1

1

1

1

1

Current transformerLZZB9-24

3

3

2

2

3

PT JDZ11-20/JDZX11-20

2

2

3

3

3

Fuse XRNP-24 0.5A

3

3

3

3

3

Grounding switch JN15-24

 

 

 

 

 

Lightning arrester HY5WZ-32/84

 

 

 

 

 

Purpose 

Metering+incoming

Metering+incoming

Metering+incoming

Metering+incoming

Metering+incoming

Scheme No.

16

17

18

19

20

 

Primary circuit scheme

image.png 

image.png 

image.png 

image.png 

image.png 

Rated current

630~3150

Primary main electrical components

Vacuum circuit breaker VS1-24

1

 

 

 

 

Current transformerLZZB9-24

3

 

3

 

 

PT JDZ11-20/JDZX11-20

3

 

3

4

4

Fuse XRNP-24 0.5A

3

XRNT3

XRNT3

3

3

Grounding switch JN15-24

 

 

3

3

3

Lightning arrester HY5WZ-32/84

 

 

 

 

 

Purpose 

Metering+incoming

Transformer for Substation

Capacitor cabinet

PT+Lightning arrester

PT+Lightning arrester

Contact Us
NO.203,Weiqi road,yueqing economic development zone, Yueqing, Zhejiang, China.